How the single-phase current voltage protector works
The operation of the single-phase current voltage protector in jbh is as follows: if the measured values of voltage and current exceed the set range, the device will cut off the output power according to the set time, and if the error is fixed, it will restart the output power after the set time. It connects
Ranges and adjustable values of JBH single-phase surge protector
parameter | description | Domain | Assumption | Description |
t | Initial setup time | 1…500 seconds
|
60 | In order to protect the equipment from the sudden disconnection and disconnection of the city’s electricity, the initial start-up time is considered, which causes the protective relay to connect with a delay when the electricity is connected.
|
U1 | The amount of overvoltage | 230 … 300 volts
|
245 | It determines the amount of acceptable overvoltage, which according to the standard can be up to 255 volts, but the default of this device is 245 volts. |
tU1 | Time to make a cut off the addition of a tag
|
0.1 … 30 seconds
|
0.1 | It refers to the time when after the occurrence of overvoltage, the protector cuts off, and it is better to set it in the shortest possible time |
U2 | Overvoltage recovery amount
|
225 … 295 volts
|
240 | It refers to the voltage that allows connection after overvoltage by reaching this protective voltage, which is set to 5 volts lower than overvoltage according to the standard. |
tu2 | Overvoltage connection delay time | 1 … 500 seconds
|
60 | It refers to the time when after the occurrence of overvoltage, the protector allows reconnection, which should be set above 1 minute. |
U3 | The amount of voltage drop
|
140 … 210 volts
|
200 | It refers to the voltage that allows connection after the voltage drop occurs, reaching this protective voltage, which is set to be 5 volts higher than the voltage drop according to the standard.
|
tU3 | Voltage drop cut-off operation time
|
0.1 … 30 seconds
|
3 | It refers to the time when after the occurrence of overvoltage, the protector allows reconnection, which should be set above 1 minute. |
U4 | Voltage drop recovery amount
|
145 … 215 volts
|
205 | It refers to the voltage that allows connection after the voltage drop occurs, reaching this protective voltage, which is set to be 5 volts higher than the voltage drop according to the standard.
|
tu4 | Delay time in voltage drop connection
|
1 … 500 seconds
|
60 | It refers to the time when after the voltage drop occurs, the protector allows reconnection, which should be set above 1 minute. |
c | Overload amount
|
1 … 63 amperes
|
32 | Determines the amount of acceptable overload that the user should determine according to the upstream fuse amp and downstream consumption. |
t1c | Overload cutoff operation time
|
0.1 … 30 seconds
|
3 | It refers to the time when the protector cuts off after the occurrence of overload, which should be set between 1 and 3 seconds considering the starting current of the equipment. |
t2c | Overload connection delay time
|
1 … 500 seconds
|
60 | It refers to the time that after overload occurs, the protector allows reconnection, which should be set above 1 minute. |
cF | Define the number of overload reconnection times
|
1…20 bar/off
|
3 | When an overload occurs, after the defined period of time, the protector connects again. When multiple overloads occur, by defining this parameter, the protector is prevented from connecting too much. |
Uc | Voltage calibration
|
-9.5 … +9.5 percent
|
% | This parameter needs to be changed when the voltage display shows a higher or lower value than the actual value. By reducing or increasing the percentage, the actual voltage can be reached with high accuracy. |
Cc | Current calibration
|
-9.5 … +9.5 percent
|
% | This parameter needs to be changed when the current display shows a higher or lower value than the actual value, and by reducing or increasing the percentage, the actual current can be reached with high accuracy. |
Protections
Overvoltage protection (over voltage protection) |
Voltage drop protection (under voltage protection) |
Protection against surge voltage or lightning (nole failure) |
Protection against surge voltage or lightning (lightning & surge protection) |
Overload protection (overload protection) |
Capabilities
Voltage display (voltage display) |
Display the last error (fault inquiry) |
Ability to install on rails (35mm din rail)
|
Reconnect after fixing the error (automatic recovery)
|
|
Ability to calibrate voltage (adjustable parameters)
|
Has an error indicator (fault indicator) | Ability to set time (active time adjustable) | Automatic reset capability (automatic reset) | Wide range of settings (wide range) |
Current display(current display) |
Applications of single-phase current voltage protection
Specifications of JBH single-phase overvoltage protection
Number of configurable parameters | parameters | current suffering | Product Code | Product Name | Shape | |
15 | over voltage: 230-300V Under Voltage: 140-210V Over Load : 1-63A action time: 0.1-30 Sec Recovery time: 1-500 Sec |
63A 80A |
P42063A1 P42080A1 |
CVP Current Voltage Protector |
|
Technical specifications of JBH single-phase current voltage protector
Voltage supply: 230…400 Vac | 1 | ||||
operating temperature: -30 … 70 Celsius | 2 | ||||
frequency : 50Hz/60Hz | 3 | ||||
Power Consumption : < 2W | 4 | ||||
electrical life: 100.000 times | 5 | ||||
Mechanical life: 1.000.000 times | 6 | ||||
surge protection capacity: 175 Joules | 7 | ||||
Max current / Spike voltage: 6000A/1.5KV | 8 | ||||
voltage measuring accuracy : <1% | 9 | ||||
current measuring accuracy : <1% | 10 | ||||
rated insulation voltage: 600 Vac | 11 | ||||
protection degree: IP40 for front panel & IP20 for terminals | 12 | ||||
pollution degree: 3 | 13 | ||||
operation position :any | 14 | ||||
over voltage category: III | 15 | ||||
Install way: DIN-rail mounting | 16 | ||||
Efficiency : 97% | 17 | ||||
Warranty : 3 years | 18 | ||||
Altitude above sea: no more than 2000 m | 19 | ||||
humidity : <90% | 20 | ||||
category : AC7-a | 21 | ||||
action time: <300ms | 22 |
Tips for installing a single-phase current voltage protector
Physical dimensions of current voltage protector
Cut-off curve of flow voltage governor
T: initial start-up time U1: amount of overvoltage tU1: operation time of overvoltage cutoff U2: amount of overvoltage recovery tU2: delay time of connecting overvoltage U3: amount of voltage drop tU3: delay time of cutoff of voltage drop U4: amount of drop recovery Voltage tU4: delay time in connecting voltage drop Uc: voltage calibration
How to fix errors and troubleshoot
Row | Description | parameter | code | Assumption | Description | ||||||
1-1 | The protector cuts off repeatedly | Check the high voltage limit | u1 | 245 | The voltage of the line may be above 245 volts, according to the standard, this number can be increased to 255 volts | ||||||
1-2 | Check the low voltage limit | u3 | 200 | The voltage of the line may be below 200 volts, according to the standard, this number can be reduced to 170 volts | |||||||
1-3 | Check the adjustable amp | c | 32 | If the consumption current is higher than 32 amps, this number can be increased up to 63 amps | |||||||
1-4 | Overload cutoff delay time | t1c | 3 | It is possible that the protection cut-off is due to the long start-up time of some devices, which can be increased | |||||||
2-1 | The protector does not cut off | Test the relay manually | Shasti Power | By pressing the power button, check the status of disconnection and connection of the relay, if it does not disconnect, refer to the warranty unit | |||||||
2-2 | Check the high voltage limit | u1 | 245 | The upper limit voltage can be reduced to 235 volts for very special protections | |||||||
2-3 | Check the low voltage limit | u3 | 200 | The lower limit voltage can be increased up to 215 volts for very special protections | |||||||
2-4 | High limit cutoff delay time | tu1 | 0.1 | Set this parameter below 1 second | |||||||
2-5 | Delay time in low cutoff | tu3 | 3 | Set this parameter below 3 seconds | |||||||
2-6 | Check the adjustable amp | c | 32 | The overload current is more than required | |||||||
2-7 | Overload cutoff delay time | t1c | 3 | Set this parameter below 5 seconds | |||||||
3-1 | The protector disconnects but does not reconnect | Check the high limit recovery voltage | u2 | 240 | Set this parameter 5 to 10 volts lower than U1 parameter | ||||||
3-2 | Check the delay time in connecting the upper limit | tu2 | 60 | Set this parameter below 240 seconds | |||||||
3-3 | Check the low limit recovery voltage | u4 | 205 | Set this parameter 5 to 10 volts higher than the U3 parameter | |||||||
3-4 | Check the delay time in connecting the lower limit | tu4 | 60 | Set this parameter below 240 seconds | |||||||
3-5 | Check the delay time in the overload connection | t2c | 60 | Set this parameter below 240 seconds | |||||||
3-6 | Check the number of reconnection of the overload error | cf | 3 | If not needed, turn off this parameter | |||||||
4 | The protective voltage is different from the mains voltage | Voltage calibration | uc | 0 | The voltage can be calibrated with high accuracy by increasing or decreasing the step | ||||||
During startup, the protective relay is connected without delay or with a long delay | Check startup time | t | 60 | Set this parameter below 240 seconds |
محمد امین –
استفاده کردم. بسیار عالی بود
عبدالجلیل ملک زاده –
سلام ودرودبسیارعالی است ولی درهنگام استارت کولرگازی برق روقطع میکنه درکاتالوگ تنظیم درمورداین مسئله چیزی نگفته
عبدالجلیل ملک زاده –
عالی
علی سلیمی –
با سلام. من محافظ جریان تک فاز یک هفته هست که نصب کردم. وتا حالا خوب خودشو نشون داده. و چیزی دیگه ای که هست نصب اسان وراحت داره
Reza –
سلام ودرود
ممنون از لطف و نظر شما
علی سلیمی –
با سلام. من محافظ ولتاژ جریان تک فاز یک هفته هست که نصب کردم. وتا حالا خوب خودشو نشون داده. و چیزی دیگه ای که هست نصب اسان وراحت داره